Schneider Electric Easypact EZC MCCB EZC100B 40A 3P/3d – EZC100B3040
range of product :EasyPact
product or component type :Circuit breaker
device short name :Easypact EZC100B
circuit breaker name :Easypact EZC100B
device application :Distribution
poles description :3P
protected poles description :3t
network type :
DC
AC
network frequency :50/60 Hz
[In] rated current :100 A at 40 C
[Ui] rated insulation voltage :690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage :6 kV conforming to IEC 60947-2
[Ue] rated operational voltage :550 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity code :B
breaking capacity :
10 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity :
0.625 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
1.25 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
1.875 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
1.875 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolation :Yes conforming to IEC 60947-2
utilisation category :Category A
trip unit name :TM-D
trip unit technology :Thermal-magnetic
trip unit rating :40 A at 50 C
protection type :
Overload protection
Short-circuit protection
pollution degree:
3 conforming to IEC 60664-1
3 conforming to IEC 947-1
Produk dijamin ASLI dan Bergaransi
Jam Kerja: 09.00 – 16.00
Hari Kerja Senin s.d Jum’at (Sabtu, Minggu dan Hari Libur Nasional OFF ~ Tidak ada pengiriman dan slow response)
There are no reviews yet.